EOLR-1 Power Supervision Relay
| Terminal | Group | Function | Connects to | |
|---|---|---|---|---|
| Red | Power | Power input + | Flag | |
| Black | Power | Power input − | Flag | |
| Violet | Relay | Common | Flag | |
| Violet | Relay | Normally open | Flag |
| Voltage | 9–40 VDC (9–35 Vrms unfiltered FWR) |
|---|---|
| Current | 20 mA max |
| Contacts | 0.5 A @120 VAC, 3 A @30 VDC resistive |
| Form | SPST normally open |
| Leads | 8 in min |
Used as an end-of-line device in fire alarm systems, e.g. to supervise power supplies
Four wire nuts included
EOLR-1 End of Line Supervision Relay · I56-2185-004 rev 004
Values from I56-2185-004 rev 004.
Verify against the manufacturer's install guide.