9600 Electric Strike
| Terminal | Group | Function | Connects to | |
|---|---|---|---|---|
| Red | Solenoid | + supply (12 V: join with Violet; 24 V: alone) | Flag | |
| Violet | Solenoid | 12 V: join with Red to +; 24 V: join with Black | Flag | |
| Black | Solenoid | 12 V: join with Red/green to −; 24 V: join with Violet | Flag | |
| Red/green | Solenoid | − supply | Flag | |
| White / Orange / Green | LBM option | Latchbolt monitor C / NO / NC | Flag | |
| Brown / Blue / Yellow | LBSM option | Latchbolt strike monitor C / NO / NC | Flag |
| Voltage | 12 or 24 VDC continuous duty |
|---|---|
| Current | 500 mA @12 V, 250 mA @24 V |
| Resistance | 24 Ω @12 V, 96 Ω @24 V |
| Tolerance | ±10% |
| Wire gauge | 12 V: 18 ga ≤200 ft, 16 ga 200–400 ft; 24 V: 22 ga ≤300 ft, 20 ga 300–400 ft (round trip) |
| UL 1034 | 1500 lb static, 70 ft-lb dynamic, 250,000 cycles |
Verify input voltage with a meter first; >10% over rating can damage the solenoid
Fail safe negates the fire rating; don't use fail safe in fire-rated or windstorm applications
Switch states listed for an unpowered strike with the monitor unactuated (door open)
When converting LBSM to fail safe, move the monitoring switch position too
9400|9500|9600|9700|9800 Electric Strike Installation Instructions & Frame Preparation · AADSS1053638 rev © 2024 (PDF Apr 2024)
Values from AADSS1053638 rev © 2024 (PDF Apr 2024).
Verify against the manufacturer's install guide.