Altronix AL600ULACM Power Supply / Access Power Controller

Suggest a correction

Suggest a correction

A free account is required. Reports stay private until a correction is published.

AL600ULACM Power Supply / Access Power Controller

Fail safe maglock Fail secure strike Form c dry Aux reader power Facp no nonlatching Facp no latching Facp nc nonlatching Facp nc latching facp-polarity-reversal (cut J3) isolated-power (cut J1, J2)
Altronix AL600ULACMAltronix AL600ULACM Fail safe maglock. L, N connects to 115 VAC 60 Hz (L hot, N neutral), 14 AWG+. + DC − connects to 12/24 VDC 6 A to ACM8 (non power-limited). AC FAIL NC/C/NO connects to AC loss supervision, 1 A @28 VDC. BAT FAIL NC/C/NO connects to Low/missing battery, 1 A @28 VDC. + BAT − connects to Standby battery (lead acid/gel). − Power + connects to DC input from PSU board. − Control + connects to Optional isolated board power (remove J1, J2). INPUT 1–8 IN, GND connects to NO dry or open collector sink triggers. OUTPUT 1–8 NC, C, NO, COM connects to Fail-safe NC(+)/COM(−); fail-secure NO(+)/COM(−); aux C(+)/COM(−); Form C 5 A when fuse removed. FACP T, + INPUT − connects to Fire alarm interface input. FACP NC, C, NO connects to Alarm relay 1 A @28 VDC (not UL evaluated).Altronix AL600ULACMFail safe maglockPSU boardL, N115 VAC 60 Hz (L hot, N neutr…+ DC −12/24 VDC 6 A to ACM8 (non po…AC FAIL NC/C/NOAC loss supervision, 1 A @28…BAT FAIL NC/C/NOLow/missing battery, 1 A @28…+ BAT −Standby battery (lead acid/ge…ACM8− Power +DC input from PSU board− Control +Optional isolated board power…INPUT 1–8 IN, GNDNO dry or open collector sink…OUTPUT 1–8 NC, C, NO, COMFail-safe NC(+)/COM(−); fail-…FACP T, + INPUT −Fire alarm interface inputFACP NC, C, NOAlarm relay 1 A @28 VDC (not…
Altronix AL600ULACM Fail safe maglock. L, N connects to 115 VAC 60 Hz (L hot, N neutral), 14 AWG+. + DC − connects to 12/24 VDC 6 A to ACM8 (non power-limited). AC FAIL NC/C/NO connects to AC loss supervision, 1 A @28 VDC. BAT FAIL NC/C/NO connects to Low/missing battery, 1 A @28 VDC. + BAT − connects to Standby battery (lead acid/gel). − Power + connects to DC input from PSU board. − Control + connects to Optional isolated board power (remove J1, J2). INPUT 1–8 IN, GND connects to NO dry or open collector sink triggers. OUTPUT 1–8 NC, C, NO, COM connects to Fail-safe NC(+)/COM(−); fail-secure NO(+)/COM(−); aux C(+)/COM(−); Form C 5 A when fuse removed. FACP T, + INPUT − connects to Fire alarm interface input. FACP NC, C, NO connects to Alarm relay 1 A @28 VDC (not UL evaluated).

Terminals Flag

TerminalGroupFunctionConnects to
L, N PSU board 115 VAC 60 Hz (L hot, N neutral), 14 AWG+ Flag
+ DC − PSU board 12/24 VDC 6 A to ACM8 (non power-limited) Flag
AC FAIL NC/C/NO PSU board AC loss supervision, 1 A @28 VDC Flag
BAT FAIL NC/C/NO PSU board Low/missing battery, 1 A @28 VDC Flag
+ BAT − PSU board Standby battery (lead acid/gel) Flag
− Power + ACM8 DC input from PSU board Flag
− Control + ACM8 Optional isolated board power (remove J1, J2) Flag
INPUT 1–8 IN, GND ACM8 NO dry or open collector sink triggers Flag
OUTPUT 1–8 NC, C, NO, COM ACM8 Fail-safe NC(+)/COM(−); fail-secure NO(+)/COM(−); aux C(+)/COM(−); Form C 5 A when fuse removed Flag
FACP T, + INPUT − ACM8 Fire alarm interface input Flag
FACP NC, C, NO ACM8 Alarm relay 1 A @28 VDC (not UL evaluated) Flag

Key specs

Output12 or 24 VDC @ 6 A (SW1 closed = 12 V, open = 24 V)
Outputs8 fused, 3.5 A each
Acm8 main fuse10 A
Psu input fuse5 A/250 V
Standby 12v4 h: 5.5 A / 24 h: 0.5 A (40 AH)
Standby 24v4 h: 5.75 A / 24 h: 0.75 A (40 AH)
Charger0.7 A max
Enclosure15.5 x 12 x 4.5 in, holds two 12 AH batteries

Keep power-limited and non power-limited wiring 0.25 in apart

Measure output voltage before connecting devices

Batteries optional for access control; without them AC loss drops outputs

24 V needs two 12 V batteries in series

Two different 'SW1's: PSU voltage switch vs ACM8 FACP switch 1

How to wire it

  1. Connect L, N to 115 VAC 60 Hz (L hot, N neutral), 14 AWG+.
  2. Connect + DC − to 12/24 VDC 6 A to ACM8 (non power-limited).
  3. Connect AC FAIL NC/C/NO to AC loss supervision, 1 A @28 VDC.
  4. Connect BAT FAIL NC/C/NO to Low/missing battery, 1 A @28 VDC.
  5. Connect + BAT − to Standby battery (lead acid/gel).
  6. Connect − Power + to DC input from PSU board.
  7. Connect − Control + to Optional isolated board power (remove J1, J2).
  8. Connect INPUT 1–8 IN, GND to NO dry or open collector sink triggers.
  9. Connect OUTPUT 1–8 NC, C, NO, COM to Fail-safe NC(+)/COM(−); fail-secure NO(+)/COM(−); aux C(+)/COM(−); Form C 5 A when fuse removed.
  10. Connect FACP T, + INPUT − to Fire alarm interface input.
  11. Connect FACP NC, C, NO to Alarm relay 1 A @28 VDC (not UL evaluated).

Source

ACM Series Installation Guide · ACMseries rev Rev. 050819

Values from ACMseries rev Rev. 050819.

Verify against the manufacturer's install guide.

Open in builder

Related parts

Planning aid only. Values are typical and vary by manufacturer, code edition and jurisdiction. Verify with manufacturer data, NEC/NFPA/TIA and the local AHJ. HireLV is not liable for designs based on these tools.